Permit: T05CM00523

Parcel: 125050760


Addresses:

2416 E 4TH ST

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
10/20/2005 BUILDING - FINAL Approved IVRS - Inspection :*
10/14/2005 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/12/2005 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GFCI AT KITCHEN SINK DOES NOT TEST (LEFT)
2) GFCI AT KITCHEN OUTLET MISSING
3) REFRIGERATOR OUTLET TEST OPEN NEUTRAL
4) PROVIDE 10 POUND TEST WITH GAUGE PRIOR TO METER
5) SECURE DISHWASHER DRAIN HSOE TO HIGHEST POINT UNDER CABINET
6) UNABLE TO LOCATE 3 SEPERATE DEDICATED CIRCUITS 20 AMP PER PLAN