Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/20/2005 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 10/14/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 10/12/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GFCI AT KITCHEN SINK DOES NOT TEST (LEFT) 2) GFCI AT KITCHEN OUTLET MISSING 3) REFRIGERATOR OUTLET TEST OPEN NEUTRAL 4) PROVIDE 10 POUND TEST WITH GAUGE PRIOR TO METER 5) SECURE DISHWASHER DRAIN HSOE TO HIGHEST POINT UNDER CABINET 6) UNABLE TO LOCATE 3 SEPERATE DEDICATED CIRCUITS 20 AMP PER PLAN |