Permit: T05CM00521

Parcel: 125030050


Addresses:

2840 E 5TH ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
05/26/2005 FRAMING Approved IVRS - Inspection :*
1) VERIFIED APPROVED DETAIL RE: PREVIOUS INSPECTION
05/11/2005 FRAMING Partial Approval IVRS - Inspection :*
1) PARTIAL PENDING NOTE #6 DATED 5/6/05
05/06/2005 FRAMING Not ready for Inspection IVRS - Inspection :*
1) BANG PLATE KITCHEN, BEDROOM 2-PLACES
2) OUTLET IN OFFICE OLD WIRING DON'T BURY INSIDE WALL, REMOVWE WIRE OR BRING OUT FLUSH WITH A BOX
3) MASTER BEDROOM CEILING LIGHT OLD WIRING TURN BOX AROUND MAKE-UP J-BOX IN ATTIC
4) OLD COOLER SERVICE OUTLET ROOF REMOVE OR EXTEND ABOVE NEW CRICKET
5) NEED STRIKER OUTLET FOR RANGE-120 VOLT
6) NEED DETAIL DRAWING APPROVED FOR SUPPORT FOR FLOOR, AND CEILING JOIST. HEADER BEAM IN LIVING ROOM
04/26/2005 FRAMING Partial Approval IVRS - Inspection :*
1) MECH DUCTS TO GO IN ROOF THEN ROOF PLY TO BE NAILED OFF
2) NEED 2 X BLKS AT INTERIOR AND EXT. BEARING BETWEEN ROOF RAFTERS
3) NEED APPROVAL FOR FIELD MADE TRUSSES AT WEST END
04/22/2005 FRAMING Not ready for Inspection IVRS - Inspection :*