Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/03/2006 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 12/30/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COUNTER TOP RECEPTACLES 2) GFCI'S NOT PER SECTION E 3801.4, E 3801.4.1 AND E 3801.4.4 2003 IRC 3) MASTER ARC FAULT NOT TRIPPING WHEN TESTED |
|
| 12/28/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) KITCHEN OUTLETS NOT PER ELECTRICAL PLAN OR CODE 2) ARC FAULTS NOT TRIPPING WHEN TESTED |