Permit: T05CM00513

Parcel: 140440200

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/31/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/18/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ELECTRIC SUB PANEL REQUIRES AN ISOLATED NEUTRAL BAR. YOU HAVE AN ISOLATED GROUND BAR. MOVE THE BAR THAT YOU ADDED TO THE LEFT SIDE OF THE PANEL AND WIRE ALL GROUND (COPPER) WIRES TO IT. REPLACE ALL THE WHITE WIRES BACK TO THE RT BUSS BAR WHERE YOU REMOVED FROM
08/15/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ELECTRIC SUB PANEL MUST HAVE AN ISOLATED NEUTRAL BAR-GROUNDS AND NEUTRALS CANNOT BE CONNECTED
2) NO PLAN/PERMIT ON SITE