Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/11/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/21/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) ROOF: LABEL A/C DISCONNECTS 2) TIGHTEN LOOSE FITTINGS 3) COVER TO BE WEATHER PROOF WHETHER OR NOT PLUGGED IN 406.8 4) BOTH SIDES OF SERVICE NIPPLE TO BE BONDED 250.92 5) ONLY ONE CONDUCTOR TO A TERMINAL OR LUG 6) BOND JUMPERS TO BE SIZED PER 250.102 AND 250.66 7) GROUNDING ELECTRODE CONDUCTOR TO BE TO GROUNDED TERMINAL |