Permit: T05CM00502

Parcel: 12106226A


Addresses:

5502 E PIMA ST #100

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/11/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/21/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) ROOF: LABEL A/C DISCONNECTS
2) TIGHTEN LOOSE FITTINGS
3) COVER TO BE WEATHER PROOF WHETHER OR NOT PLUGGED IN 406.8
4) BOTH SIDES OF SERVICE NIPPLE TO BE BONDED 250.92
5) ONLY ONE CONDUCTOR TO A TERMINAL OR LUG
6) BOND JUMPERS TO BE SIZED PER 250.102 AND 250.66
7) GROUNDING ELECTRODE CONDUCTOR TO BE TO GROUNDED TERMINAL