Permit: T05CM00485

Parcel: 141185820

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
03/11/2005 PLUMBING - INTERMEDIATE Approved OK TO COVER
03/10/2005 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*WRAP ALL WASTE & VENT PIPING PENETRATING CONCRETE. SEE REVISED H20 DRAWING P-2 FOR CORRECT WATER PIPING SIZE. INSULATION REQUIRED ON HOT WATER PIPING. OK TO COVER
03/07/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :* WATER TEST WASTE & VENT THRU ROOF OK. 1) NEED MID SPAN SUPPORTS FOR VENT AND APPROVED HANGERS EVERY 4 FOOT ON HORIZONTAL VENT PIPING ( ABS). 2) NEED PIPE WRAPS PRIOR TO CONCRETE.