Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM00477
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/08/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
12/07/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BONDING CONDUCTORS FOR #121 & 151 ARE UNDERSIZED NEC 250.102 C 2. IDENTIFY ALL SERVICE DISCONNECTS - NEC 230.70 B 3. REPLACE BROKEN RECEPTACLE COVER 4. UNSEAL METER BASES CHECK FOR NEC 250.6 VIOLATION 5. CORRECTLY IDENTIFY PANEL DIRECTORY'S - NEC 408.4 |
|
12/04/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
11/30/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* HAVE PLANS ON SITE |
|
11/27/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PLANS HAVE CHANGED AND A THIRD SPACE HAS BEEN ADDED. NEED TO REVISE PLANS TO SHOW ACTUAL SCOPE OF WORK AND SUBMIT FOR APPROVAL. |
|
02/06/2006 | ELECTRIC - FINAL | Denied | NEED TO FINISH WIRING AND RACEWAYS | |
12/08/2005 | ELECTRIC - FINAL | Denied |