Permit: T05CM00477

Parcel: 10511040D


Addresses:

235 W WETMORE RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/08/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/07/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BONDING CONDUCTORS FOR #121 & 151 ARE UNDERSIZED
NEC 250.102 C
2. IDENTIFY ALL SERVICE DISCONNECTS - NEC 230.70 B
3. REPLACE BROKEN RECEPTACLE COVER
4. UNSEAL METER BASES CHECK FOR NEC 250.6 VIOLATION
5. CORRECTLY IDENTIFY PANEL DIRECTORY'S - NEC 408.4
12/04/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
11/30/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
HAVE PLANS ON SITE
11/27/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PLANS HAVE CHANGED AND A THIRD SPACE HAS BEEN ADDED. NEED TO REVISE PLANS TO SHOW ACTUAL SCOPE OF WORK AND SUBMIT FOR APPROVAL.
02/06/2006 ELECTRIC - FINAL Denied NEED TO FINISH WIRING AND RACEWAYS
12/08/2005 ELECTRIC - FINAL Denied