Permit: T05CM00459

Parcel: 10612017M

Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Date Description Inspector Results Comments
10/21/2005 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
10/20/2005 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
09/19/2005 PLUMBING - YARD WTR LINE/TEST Partial Approval 2" OK TO PAYVE
09/14/2005 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*
1) 1" METER-1" RPPBP-2" YARDWATER DOESN'T ADD UP PRESSURE DROP ON DOWNSTREAM SIDE WILL CAUSE DEVICE TO DUMP
2) 2" YARDWATER COVERED WITHOUT INSPECTION
3) WHERE IS STAMP FROM 3RD PARTY REVIEWER ON SITE UTILITY PLAN
08/22/2005 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*
1) PROVIDE SITE UTILITY PLAN
07/18/2005 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*