Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/28/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/21/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*OUTSIDE LIGHTING HAS BEEN CHANGED-PLAN SHOWS HPS-50W CONTRACTOR AHS INSTALLED FLOURESCENT LIGHTS SPACES NEED TO BE NUMBERED PLAN SHOW 9 TENANT SPACES BUILD OUT-ONLY 6 BUILD OUT-HAVE VERIFICATION FOR THIS CHANGE PLAN SHOWS 20 HAR? BREAKER IN PANEL UNIT ON ROOF CALL FROM MIN 15 AMP SWITCH CONDUIT TO BE STRAPPED AT 3 WAYS BY REAR DOOR. MARK AC DISCONNECT'S WITH UNIT # 'S |