Permit: T05CM00452

Parcel: 11306147B

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T05CM00452

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
04/29/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
04/20/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :* 311.4 94 UPC PROHIBITED PRACTICES-DUMPING INTO VENT 908.1 94 UPC-VERTCAL WET VENTING. DELTA ONE REVISION APPROVED IN ERROR-DID NOT DISCLOSE WATER CLOSET BELOW LAVS. SEE SECTIONS LISTED ABOVE. 2) 2" WASTER FOR P-1 IN CHASE OK TO COVER AFTER HOT PIPE INSULATED. BACK TO BACK P-3 P-5 OK TO COVER. 3) GAS PRESSURE TEST OK REVISED PLAN ON SITE.