Inspection History Details
Inspection Status: Partial Approval
Inspection History: BUILDING - FINAL
Permit Number - T05CM00440
Inspection Description - BUILDING - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/11/2006 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 1) CONDENSATE LINE TO DRAIN PER DETAIL 2) SCUPPER DUMPS ON LIGHT FIXTURE 3) PLUG HOLE IN DISCONNECT |
|
06/28/2006 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GARAGE AND CASITA: NO CONDENSATE LINE ROOF UNIT, SERVICE RECEPTACLE BUBBLE COVER TO CLOSE TO ROOF CAN'T OPEN, LABEL FOR 25/25 FUSING MAX 50/50'S INSTALLED, 2ND WHIP FOR HEAT STRIP NOT CONNECTED, STAT WIRE TO BE IN CONDUIT WITH ROOF JACK, SKIDS CENTER UNIT ON 4 X 4 2) ROOF SCUPPER DRAINS ON OUTDOOR LIGHT FIXTURE 3) ALL VENTS CAPPED WITH GEM CAP 4) NEED 1/4" ? VALVE FOR H20 5) MISSING FURNACE CAP 6) MAX 30/30 FUSES MAIN HOUSE A/C 35/40 INSTALLED 7) MUST BE ABLE TO REMOVE C/O PLUB NORTH WALL EXT. |