Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T05CM00439
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/08/2006 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
07/31/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SOUTHSIDE BLDG -- LOOK OK NORTHSIDE BLDG -- FRONT DOORS OPENING SEALED W/PLASTIC REAR DOORS -- WILL NOT OPEN! |
|
07/24/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. KITCHEN HOOD EXHAUST DUCTS -- NEED TO RUN SMOOTH PIPE (NO FLEX DUCT) ALL CRIMPED ENDS RUNNING WITH AIR FLOW. 2. DRYER VENTS TOP OF 4"X3" GALV DUCTS -- A. THERE IS A 4" GALV. ADJ. ELBOW INSERTED THAT WILL CREATE INSIDE LINT TRAP. NEED A TIGGING TO GO FROM 4"X3" DUCTS TO 4" 0 PIPE ALL CRIMPED ENDS W/AIRFLOW. B. SHT. M.1 CALLS FOR DRYER TERMINATION TO BE WITH ROOF CAP. |