Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T05CM00439
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/30/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
01/23/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. UNIT #9 REPAIR LEAK UNDER SINK ON DRAIN PIPING 2. INSTALL VACUUM BREAKER ON HOSE BIBB ON EAST SIDE OF NORTH BUILDING. 3. PROVIDE MEANS FOR WATER HAMMERING AT WASHER BOXES IN ALL UNITS. |
|
01/03/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SANTEE FOR AAV NOT APPROVED 2. COMPLETE ALL WORK BEFORE CALLING FINAL |