Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM00439
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/02/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
01/10/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SERVICE #1 1. ID ALL SERVICES WITH UNIT #'S 2. RISER TO SERVICE TO HAVE A GROUND BUSHING W/CORRECT SIZE JUMPER TO ENCLOSURE. 3. RISER RUNS CROOKED INTO CAN, INSTALL STRAP TO SUPPORT. 4. OWNERS PNL TO HAVE ALL CUTLER HAMMER BREAKERS. 5. CORRECT CONCENTRIC KO AT BOTTOM OF SERVICE TO EFFECTIVELY CLOSE OFF ENCLOSURE. 6. BOND WATER LINE TO SERVICE 7. ISOLATE NEUTRALS & GROUNDS AT OWNERS PNL. SERVICE #2 1. RISER TO SERVICE REQUIRES GROUND BUSHING & CORRECTLY CLOSE OF DAMAGED CONCENTRIC KO 2. UNITS 1-5 PANEL INSPECTED AND READY FOR TESTING POWER SUBJECT TO CORRECTIONS ON SERVICE. OTHER INSPECTIONS TO FOLLOW FOR FINALS FOR ENTIRE UNITS. BOND TO BE POSTED FOR TEMP POWER |
|
01/10/2007 | ELECTRIC - FINAL | Denied | 1. POWER BOND FOR TEMP SERVICE NOT POSTED. 2. HOMEOWNERS METER TO BE HELD UNTIL APARTMENT LIGHTING SITUATION APPROVED. 3. SOUTH SERVICE - ENTRY INTO BOTTOM OF SERVICE STILL IN BAD SHAPE, BOTTOM LOCKNUT NOT TIGHTENED, ENTRY INTO ENCLOSURE COCKED. 4. NEED NOTIFICATION AT SERVICES "NO METALLIC WATER OR GAS LINE" 5. CORRECT KO SEAL IN PANEL IN UNIT #7 ALSO #6 6. WIRING IN PNL #8 STICKING OUT OF WALL, NEEDS TO DE SET INTO PNL, ALSO #9, ALSO #10 7. ROOF AC'S CHECKED & OK, ROOF GFI'S OK |