Permit: T05CM00439

Parcel: 11707026A


Addresses:

428 S 4TH AV #01*


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM00439

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/02/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/10/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SERVICE #1
1. ID ALL SERVICES WITH UNIT #'S
2. RISER TO SERVICE TO HAVE A GROUND BUSHING W/CORRECT SIZE JUMPER TO ENCLOSURE.
3. RISER RUNS CROOKED INTO CAN, INSTALL STRAP TO SUPPORT.
4. OWNERS PNL TO HAVE ALL CUTLER HAMMER BREAKERS.
5. CORRECT CONCENTRIC KO AT BOTTOM OF SERVICE TO EFFECTIVELY CLOSE OFF ENCLOSURE.
6. BOND WATER LINE TO SERVICE
7. ISOLATE NEUTRALS & GROUNDS AT OWNERS PNL.

SERVICE #2
1. RISER TO SERVICE REQUIRES GROUND BUSHING & CORRECTLY CLOSE OF DAMAGED CONCENTRIC KO
2. UNITS 1-5 PANEL INSPECTED AND READY FOR TESTING POWER SUBJECT TO CORRECTIONS ON SERVICE.

OTHER INSPECTIONS TO FOLLOW FOR FINALS FOR ENTIRE UNITS.
BOND TO BE POSTED FOR TEMP POWER
01/10/2007 ELECTRIC - FINAL Denied 1. POWER BOND FOR TEMP SERVICE NOT POSTED.
2. HOMEOWNERS METER TO BE HELD UNTIL APARTMENT LIGHTING SITUATION APPROVED.
3. SOUTH SERVICE - ENTRY INTO BOTTOM OF SERVICE STILL IN BAD SHAPE, BOTTOM LOCKNUT NOT TIGHTENED, ENTRY INTO ENCLOSURE COCKED.
4. NEED NOTIFICATION AT SERVICES "NO METALLIC WATER OR GAS LINE"
5. CORRECT KO SEAL IN PANEL IN UNIT #7 ALSO #6
6. WIRING IN PNL #8 STICKING OUT OF WALL, NEEDS TO DE SET INTO PNL, ALSO #9, ALSO #10
7. ROOF AC'S CHECKED & OK, ROOF GFI'S OK