Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T05CM00439
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/02/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
08/14/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WIRING IN WALLS PER CODE, OK, HOWEVER DO NOT REFLECT APPROVED PLANS, ALL WIRING PANELS, ETC MUST BE ON REVISED PLANS PRIOR TO NEXT INSPECTION. IF NOT ELECTRICAL CONTR. TO WIRE PER APPROVED PLANS. |
|
08/08/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* REVISIONS ON APPROVED PLANS BY ARCH/ENGINEER LETTER FROM ENGINEER NOT SUFFICIENT, SEE NOTES INSP. ON 7/24/06 |
|
07/25/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
07/24/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PANEL FEEDERS ON SITE #1 - 100 AMP - 75 DEG. COLUMN PLAN SHOWS 150 AMP CB -- 110 AMP ON SITE PLAN SHOWS 120A CALCULATED LOAD, ALSO 3 1/0 COPPER FOR FEEDERS. 2. ADDITIONAL 40 AMP COOKTOP LOAD ADDED. 3. TOP FLOOR STAIRWAY WALL ADDED 4. LIGHT CHANGED COMPLETELY INSIDE & OUT 5. 1 FAN INSTEAD OF TWO - PLEASE ADDRESS CHANGES NOT PER PLAN. |