Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM00439
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/17/2006 | FRAMING | Approved | IVRS - Inspection :* | |
08/11/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* FIREBLOCKING & DRAFT STOP INCOMPLETE |
|
08/08/2006 | FRAMING | Not ready for Inspection | IVRS - Inspection :* A. AREA SEPARATION @ EXTERIOR ROOF SOFFIT OK B. FURROUT AT SHEAR WALL OK PER RFI DATED 7/31/06 (ATTACHED) 1. FIX DAMAGED STUDS 2. REPAIR DAMAGED FIRE BLOCKS AT CEILING AND SOFFIT LINES. 3. TIGHTEN ALL LOOSE NUTS ON ANCHOR BOLTS. 4. STAIR TREAD RISERS OUT OF COMPLIANCE, EXCESSIVE VARIATION FROM TOP TO BOTTOM. 5. PROVIDE REVISED PLAN FOR DELETION OF 2HR DEMISING WALL. |
|
07/21/2006 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1. A 1 HOUR RATED SYSTEM MUST BE PROVIDED @ ROOF POPOUT @ EACH AREA SEPARATION WALL. 2. EVERY 10 FT. OF POPOUT REQUIRES FIREBLOCK 3. YOU MAY TRY TO REVISE DEMISING WALL FROM 2 HOUR ON PLAN PER SECTION 706 TO EXCEPTION 2 SECTION 708.3 (5/8" ROCK EVERYWHERE, EASIER TO FIRESTOP) 4. I NEED TO SEE ALL FIREBLOCK OPENINGS FORMED IN 5. REVISE LENGTH OF SHEAR DEMISING WALL FOR LAUNDRY FURROUT. |