Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/09/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 05/23/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. POST YOUR ADDRESS 2. PROVIDE PARKING & ACCESS 3. A1 REVISION DOES NOT PROVIDE FOR 1 HOUR DEMISING WALL SEPARATION. 4. DETAIL 3/a9 DOES NOT APPLY TO REFERENCED PAGE. 5. DESIGN PROFESSIONAL NEEDS TO ADDRESS 1 HOUR SEPARATION AT WALL POPOUTS AND FIRESTOP FOR FIREWALL PENETRATIONS. 6. YOU NEED TO EXTEND SHEETROCK SHEAR WALLS (SW1) TO ROOF DECK. 7. PROVIDE ENGINEER APPROVAL FOR SUBSTITUTION OF STAPLES FOR 8d NAILS IN SW2. |