Inspection History Details
Inspection Status: Approved
Inspection History: ROOF NAILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/21/2005 | ROOF NAILING | Approved | IVRS - Inspection :* | |
| 08/08/2005 | ROOF NAILING | Partial Approval | IVRS - Inspection :* 1) PARTIAL ROOF NAILING, DRY IN AT OWN RISK. MAX HEIGHT OF 10'-6" DOES NOT MATCH NEW BLDG HEIGHT OF 11'-8", RESUBMIT TO ZONING FOR APPROVAL 2) CLIP EVERY OTHER STUD 3) STRAP HEADER 4) REPLACE KING STUD AT DOOR OVER NOTCHED 5) TRUSSES NOT BRACED PER TRUSS DRAWINGS |
|
| 08/03/2005 | ROOF NAILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REVISE PLANS, TO AS BUILT, SEE LAST INSPECTION |
|
| 08/02/2005 | ROOF NAILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED REVISION APPROVED BY CITY OF TUCSON FROM LPI'S TO TRUSSES 2) NEED TRUSS CALC'S 3) HEIGHT OF BLDG CHANGED, REVISE PLANS |