Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T05CM00419
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/11/2005 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
05/24/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TO MANY PERSONAL ITEMS IN GARAGE-SOMEONE MUST BE PRESENT |
|
02/25/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ANCHOR BOLTS REQUIRED WITHIN 12" OF EACH BOTTOM PLATE END OR SPLICE AND A MINIMUM OF 2 ANCHOR BOLTS REQUIRED IN EACH PLATE/BOARD 2) ONE TRUSS CUT/NOTCHED IN 12 PLACES, HAVE TRUSS MANUFACTURER PROVIDE AN APPROVED REPAIR 3) CROSS BRACE 3 TRUSSES EACH END 4) INSTALL EXTERIOR PANELING ON WALLS 5) NO CITY APPROVED PLANS ON SITE 6) ROOF SHEATHING NAILING IS PER CODE |