Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/15/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 09/18/2006 | FRAMING | Partial Approval | IVRS - Inspection :* 1) APPROVED TO INSTALLL STUCCO MESH AND PROCEED WITH TRADES 2) HINGE BRACING NOT PER PLAN 3) DBL 2 X 8 HEADER MISSING PER PLAN |
|