Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/31/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* SEAL WALL PENETRATIONS. 725 W. 41ST ST -- YOU STILL NEED TO SEAL WALL PENETRATIONS. I DO NOT KNOW WHY YOUR ROUGH SOIL, HCS, AND INTERMEDIATE DID NOT GET APPROVED. I CANNOT SEE THESE AREAS BECAUSE THEY HAVE BEEN, COVERED THEREFORE. I CANNOT APPROVE THESE INSPECTIONS. |
|
| 03/27/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE A WATER TEST ON SHOWER PANS; PLUG DRAIN AND FILL TO FLOOD LEVEL. 2. PROVIDE RIGID PIPING FOR TEMPERATURE AND PRESSURE RELIEF DRAIN. 3. MAKE CLEAN OUT PLUGS WATER AND GAS TIGHT. 4. CLEAN OUT COVERS MISSING IN LAUNDRY. 5. SEAL WALL PENETRATIONS. 6. PROTECT ABS VENT TERMINATIONS W/LATEX PAINT. |
|
| 03/24/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ACCESS REQUIRED 725 W 41ST ST ALL UNFINALED INSPECTIONS MUST BE CALLED IN FOR INSPECTION BEFORE PLUMBING CAN BE FINALED. PROVIDE INSPECTION HISTORY PROVING THAT THESE ITEMS ARE OK 03005-03055-03035 AND ALL OTHERS. PROVIDE ACCESS TO JOB, PLANS AND PERMIT CARD. HAVE TUBS FILLED TO OVERFLOW LEVEL AND SHOWER PANS TESTED TO FLOOD RIM IF NOT INSPECTED. SEAL WALL PENETRATIONS. FLEX NOT ALLOWED ON T&P |