Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/07/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/04/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. 2 GFI PROTECTED CKTS ARE REQUIRED FOR KITCHEN COUNTERTOP RECEPTS. 2. BEDROOMS MUST BE ON ARC FAULT CIRCUIT BREAKER. 735 W 1ST ST 1. CODE REQUIRES 2 ELECTRICAL CIRCUITS TO SERVE KITCHEN COUNTERTOP RECEPTS, MUST BE GFI PROTECTED ALSO BEDROOMS MUST BE ARC FAULT PROTECTED. 2. THERE IS AN ARC FAULT BREAKER IN PANEL -- SHOULD BE FOR BEDROOM CKTS. |
|
| 03/24/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE NOTES FOR 725 NOTES: 1. COUNTERTOP KITCHEN RECEPTS, MUST BE GFI PROTECTED PER NEC 2. DISCONNECTS FOR AC CONDENSERS OUTSIDE IN VIOLATION OF 110-26 NEC FOR WORKING CLEARANCE MUST HAVE 36" IN FRONT BY 30" WIDE OF WORKING SPACE. 3. ELECTRIC WATER HTRS MUST HAVE DISCONNECT 4. BUBBLE COVERS REQUIRED FOR GFI RECEPTS OUTSIDE. |