Permit: T05CM00402

Parcel: 119032750


Addresses:

725 W 41ST ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/07/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/04/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. 2 GFI PROTECTED CKTS ARE REQUIRED FOR KITCHEN COUNTERTOP RECEPTS.
2. BEDROOMS MUST BE ON ARC FAULT CIRCUIT BREAKER.
735 W 1ST ST
1. CODE REQUIRES 2 ELECTRICAL CIRCUITS TO SERVE KITCHEN COUNTERTOP RECEPTS, MUST BE GFI PROTECTED ALSO BEDROOMS MUST BE ARC FAULT PROTECTED.
2. THERE IS AN ARC FAULT BREAKER IN PANEL -- SHOULD BE FOR BEDROOM CKTS.
03/24/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SEE NOTES FOR 725
NOTES:
1. COUNTERTOP KITCHEN RECEPTS, MUST BE GFI PROTECTED PER NEC
2. DISCONNECTS FOR AC CONDENSERS OUTSIDE IN VIOLATION OF 110-26 NEC FOR WORKING CLEARANCE MUST HAVE 36" IN FRONT BY 30" WIDE OF WORKING SPACE.
3. ELECTRIC WATER HTRS MUST HAVE DISCONNECT
4. BUBBLE COVERS REQUIRED FOR GFI RECEPTS OUTSIDE.