Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2006 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection | |
| 02/28/2006 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : The service is not per code.| 210* 1. SERVICE WEATHERHED TO BE ABOVE STRIKE KNOB NEC 23O.54(C) 2. TIGHTEN ALL BONDING/SET SCREWS, ETC. NEC 250.4 3. BOND ALL METAL PIPING SYSTEMS TO SERVICE ENCLOSURE NEC 250.104 4. IDENTIFY SERVICE DISCONNECT NEC 230.70(B) |