Permit: T05CM00401

Parcel: 11704226A


Addresses:

510 N STONE AV

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
03/02/2006 ELECTRIC - CABLE DROP Approved IVRS - Inspection
02/28/2006 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
The service is not per code.| 210*
1. SERVICE WEATHERHED TO BE ABOVE STRIKE KNOB NEC 23O.54(C)
2. TIGHTEN ALL BONDING/SET SCREWS, ETC. NEC 250.4
3. BOND ALL METAL PIPING SYSTEMS TO SERVICE ENCLOSURE NEC 250.104
4. IDENTIFY SERVICE DISCONNECT NEC 230.70(B)