Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/22/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/18/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) BOND NEUTRALS IN SERVICE DISCONNECTS AND BOND BUSHINGS IN SERVICE DISCONNECTS 2) LABELS DISCONNECTS AT SERVICE WITH PERMANENT LABELS AS TO LOAD SERVED 3) EXPOSE GROUND RODS FOR INSPECTION BLDG STEEL 4) NEED TO INSPECT FEEDER TIE-IN TO CT CAN PRIOR TO RELEASE FOR CLEARANCE TO TEP |