Permit: T05CM00367

Parcel: 13601008G

Inspection Status: Approved

Inspection History: SITE - SEWER

Date Description Inspector Results Comments
05/10/2006 SITE - SEWER Approved IVRS - Inspection :*
REVISED APPROVED PLAN ON SITE
10/04/2005 SITE - SEWER Partial Approval IVRS - Inspection :*6" SEWER INSTALLED IN PLACE OF 4" FORM NEW MANHOLE NORTH THEN EAST TO NEW BLDG (OFFICE) WATER TEST OK
WILL NEED VERIFICATION OF GRADEON SEWER
WILL NEED VACUUM TEST ON MANHOLE
6" STUB TO NORTHEAST TO BE INSTALLED PER PLAN WITH TEST OR PROVIDE REVISED CITY APPROVED PLAN
09/30/2005 SITE - SEWER Denied IVRS - Inspection :
See detailed listing on site.| 999*CLEAN OUTS TO BE AT 100' INTERVALS INCLUDING RISE.
WILL REQUIRE VERIFICATION OF GRADE ON ENTIRE SEWER
WILL REQUIRE VACUUM TEST OF MANHOLE
6" STUB FROM MANHOLE EAST TO BE PER PLAN OK.PROVIDE CITY APP. REVISED APPROVED PLAN.