Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM00366
Inspection Description - ELECTRIC - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/26/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. THE CONDUIT AT BUILDING 11 WHERE IT COMES UP TO J-BOX MUST BE 18" DEEP - NOW 4" 2. CONDUIT TO ALSO BE 18" DEEP AT BLD 12 3. ID DISCONNECT PERMANENTLY AT BLD 12 FOR GATE 4. OK TO COVER TRENCHING IN BETWEEN |
|
09/06/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ONLY 6 MAINS ALLOWED ON ONE DROP FROM UTILITY THIS METER (OWNERS) MAKES 7TH 2. LABEL THIS SERVICE "GATE OPERATOR" 3. CIRCUIT INSIDE TO BE TERMINATED AND IDENTIFIED |
|
08/28/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOT READY |
|
08/23/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HAVE INSTALLER MEET ME TO OPEN AND UNLOCK EQUIPMENT 2. PROVIDE PLANS TO GATE OPENER |
|
06/30/2005 | ELECTRIC - FINAL | Partial Approval | ||
06/28/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |