Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/21/2005 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :* OK FINAL |
| 03/16/2005 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :* 1) BOXES MORE THAN 1/4" FROM SURFACE TO BOX NEED AN APPROVED EXTENDER RING 314.20. 2) LABELING FOR MAIN DISCONNECT AND TRANSFORMER TO BE PERMANENT. 3) PLANS CALL FOR 45 A FUSES. WE HAVE 60A INSTALLED. 4) SECURE TRANSFORMER TO FLOOR PAD. |