Permit: T05CM00362

Parcel: 12701005D

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM00362

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/21/2005 ELECTRIC - FINAL Approved IVRS - Inspection :* OK FINAL
03/16/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* 1) BOXES MORE THAN 1/4" FROM SURFACE TO BOX NEED AN APPROVED EXTENDER RING 314.20. 2) LABELING FOR MAIN DISCONNECT AND TRANSFORMER TO BE PERMANENT. 3) PLANS CALL FOR 45 A FUSES. WE HAVE 60A INSTALLED. 4) SECURE TRANSFORMER TO FLOOR PAD.