Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM00362
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/21/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL | |
03/16/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BOXES MORE THAN 1/4" FROM SURFACE TO BOX NEED AN APPROVED EXTENDER RING 314.20. 2) LABELING FOR MAIN DISCONNECT AND TRANSFORMER TO BE PERMANENT. 3) PLANS CALL FOR 45 A FUSES. WE HAVE 60A INSTALLED. 4) SECURE TRANSFORMER TO FLOOR PAD. |