Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/14/2005 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection :* OK TO TILE |
| 03/07/2005 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection :* 1) SUPPORT M/C CABLES WITHIN 12" OF BOXES AND 6' INTERVALS 2) VDV CABLE TO BE SUPPORTED AT 6' INTERVALS WITH SUPPORTS AND UP OFF OF GRID. 725.6 & 800.6. 3) WHERE ARE ON SITE PLANS? |