Permit: T05CM00362

Parcel: 12701005D

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T05CM00362

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
03/14/2005 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :* OK TO TILE
03/07/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :* 1) SUPPORT M/C CABLES WITHIN 12" OF BOXES AND 6' INTERVALS 2) VDV CABLE TO BE SUPPORTED AT 6' INTERVALS WITH SUPPORTS AND UP OFF OF GRID. 725.6 & 800.6. 3) WHERE ARE ON SITE PLANS?