Permit: T05CM00353

Parcel: 115071540


Addresses:

118 E ELM ST #01

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/11/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/07/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. KIT EX FAN NEEDS BUSHING FOR ROMEX, GROUND SCREW TO HAVE ONE WRAP AND TIGHTEN SCREW.
2. INSULATION ON ROMEX AT WH DISCONNECT TO ENTER DISCONNECT.
3. DISCONNECT FOR WH #2 NOT MOUNTED PROPERLY ROCKS TOP TO BOTTOM.
4. NEED ACCESS TO ROOF.
04/04/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
CONTRACTOR DID NOT SHOW UP WAITED 15 MIN.