Permit: T05CM00328

Parcel: 122154490

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/14/2005 ELECTRIC - FINAL Approved IVRS - Inspection :* OK TO CLEAR FOR METER SET & PERM POWER
06/13/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* THE SEISMIC WIRES TO THE RECESSED LIGHTING FIXTURES MUST BE ATTACHED TO THE FIXTURES FIRST ( OR ONLY). THEY MAY BE USED FOR CASUAL SUPPORT OF FIXTURE WHIP ( FACTORY OR FIELD CUT MC CABLE). RUNS OF CONDUIT MUST BE SUPPORTED BY SEPARATE SUPPORT WIRES. THESE MUST BE TIED TOP & BOTTOM ( GRID) . 1/2" FLEX CONDUIT DOES NOT QUALIFY AS FIXTURE WHIPS. SEE NEC ART 300 & 420 LIGHTING FIXTURES.
06/10/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The fixtures are not per plans and specifications.| 250*
06/08/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920* NO ACCESS, LOCKED, NO ONE ON SITE. NO INSPECTION. RECALL