| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/14/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK TO CLEAR FOR METER SET & PERM POWER | |
| 06/13/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* THE SEISMIC WIRES TO THE RECESSED LIGHTING FIXTURES MUST BE ATTACHED TO THE FIXTURES FIRST ( OR ONLY). THEY MAY BE USED FOR CASUAL SUPPORT OF FIXTURE WHIP ( FACTORY OR FIELD CUT MC CABLE). RUNS OF CONDUIT MUST BE SUPPORTED BY SEPARATE SUPPORT WIRES. THESE MUST BE TIED TOP & BOTTOM ( GRID) . 1/2" FLEX CONDUIT DOES NOT QUALIFY AS FIXTURE WHIPS. SEE NEC ART 300 & 420 LIGHTING FIXTURES. | |
| 06/10/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The fixtures are not per plans and specifications.| 250* |
|
| 06/08/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* NO ACCESS, LOCKED, NO ONE ON SITE. NO INSPECTION. RECALL |