Permit: T05CM00328

Parcel: 122154490

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
06/14/2005 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
06/13/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
06/10/2005 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The fixtures are not per plans and specifications.| 250*
1) THE DROP IN FIXTURES MUST BE MECHANICALLY FASTENED TO T-BAR. PREFER TWO SCREWS-CENTER OF EACH END. CLIPS MAY BE USED IF PROPERLY APPLIED PER MANUFACTURERS INSTRUCTIONS
2) SEISMIC WIRES MISSING ON FEW
3) SEISMIC WIRES ON RECESSED FIXTURES MUST BE ATTACHED TO BODY FRAME-NOT TO BRACKET
4) SUPPORT WIRES TO 1/2" FLEX MUST BE SEPERATE FROM GRID WIRES-TIE TOP AND BOTTOM
5) ROOF MOUNTED DISCONNECTS ARE LOOSE. SECURE TO ROOF OR UNIT (BRACE). CANNOT BE SUPPORTED BY CONNECTING CONDUIT FITTING
06/08/2005 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
There is no access to the site.| 920*
04/15/2005 ELECTRIC - ABOVE CEILING Cancelled IVRS - RI canceled
04/13/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*1) THE SOFFIT OVER RECEPTION IS APPROVE 2. THE SOFFIT OVER CONFERENCE ROOM IS INCOMPLETE ( ELECTRICALS). 3) THE SOFFIT IN THE CONFERENCE ROOM IS NOT IN PLAN. A REVISION IS IN ORDER. 4) CALL FOR INTERMEDIATE INSPECTION. WALLS, EXCEPT BATHS & BREAKS ROOM, APPEAR TO BE ROUGH-IN COMPLETE