Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/14/2005 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 06/13/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 06/10/2005 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The fixtures are not per plans and specifications.| 250* 1) THE DROP IN FIXTURES MUST BE MECHANICALLY FASTENED TO T-BAR. PREFER TWO SCREWS-CENTER OF EACH END. CLIPS MAY BE USED IF PROPERLY APPLIED PER MANUFACTURERS INSTRUCTIONS 2) SEISMIC WIRES MISSING ON FEW 3) SEISMIC WIRES ON RECESSED FIXTURES MUST BE ATTACHED TO BODY FRAME-NOT TO BRACKET 4) SUPPORT WIRES TO 1/2" FLEX MUST BE SEPERATE FROM GRID WIRES-TIE TOP AND BOTTOM 5) ROOF MOUNTED DISCONNECTS ARE LOOSE. SECURE TO ROOF OR UNIT (BRACE). CANNOT BE SUPPORTED BY CONNECTING CONDUIT FITTING |
|
| 06/08/2005 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : There is no access to the site.| 920* |
|
| 04/15/2005 | ELECTRIC - ABOVE CEILING | Cancelled | IVRS - RI canceled | |
| 04/13/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*1) THE SOFFIT OVER RECEPTION IS APPROVE 2. THE SOFFIT OVER CONFERENCE ROOM IS INCOMPLETE ( ELECTRICALS). 3) THE SOFFIT IN THE CONFERENCE ROOM IS NOT IN PLAN. A REVISION IS IN ORDER. 4) CALL FOR INTERMEDIATE INSPECTION. WALLS, EXCEPT BATHS & BREAKS ROOM, APPEAR TO BE ROUGH-IN COMPLETE |