Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T05CM00325
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/26/2005 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
07/22/2005 | BUILDING - FINAL | Denied | 1) LABEL SMOKE DETECTOR CIRCUIT IN PANEL 2) WATER HEATER VENT REQUIRES 3 SCREWS AT CONNECTION 3) GFCI PROTECTED OUTLETS REQUIRED WITHIN 24" EITHER SIDE OF KITCHEN SINK AND RT OF RANGE 4) ALL BEDROOM OUTLETS MUST BE ARC FAULT PROTECTED 5) 110 VOLT A/C SMOKE DETECTORS IN BEDROOMS MUST BE ARC FAULT PROTECTED 6) NO ATTIC LIGHT 7) NO FURNACE SPARK SHIELD 8) CERTS |