Permit: T05CM00323

Parcel: 140376520


Addresses:

6890 S HARRIER LP

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
05/10/2005 FRAMING Approved IVRS - Inspection :*
05/09/2005 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) RED HEAD ANCHOR BOLTS LOOSE
2) UPPER AND LOWER COMBUSTION AIR CANNOT BE CONNECTED-BLOCK EDGES
3) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACE
4) WIRING NOT COMPLETE AT KITCHEN
5) GFCI OUTLET REQUIRED WITHIN 24" OF KITCHEN SINK
6) NO GAS PRESSURE TEST
7) PLUMBING OUT OF WALL CAVITY
8) STOPPED INSPECTION, TO MANY ITEMS