Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/10/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 05/09/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) RED HEAD ANCHOR BOLTS LOOSE 2) UPPER AND LOWER COMBUSTION AIR CANNOT BE CONNECTED-BLOCK EDGES 3) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACE 4) WIRING NOT COMPLETE AT KITCHEN 5) GFCI OUTLET REQUIRED WITHIN 24" OF KITCHEN SINK 6) NO GAS PRESSURE TEST 7) PLUMBING OUT OF WALL CAVITY 8) STOPPED INSPECTION, TO MANY ITEMS |