Permit: T05CM00322

Parcel: 140324860

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T05CM00322

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
04/14/2005 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
04/12/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ITEMS 2, 4, 6, 6 AND 7 FROM 4/8/05 NOT COMPLIED WITH
04/08/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GARAGE MAS CLIPS NOT NAILED
2) CLIP ENDS OF GABLE END TRUSS 1/D-2
3) DRAG BRACE NOT INSTALLED PER 13/D-5
4) SHEAR WALL 4 NOT NAILED PER PLAN
5) 2/D-2 NOT COMPLIED WITH FRONT HOUSE
6) X BRACE TRUSS EACH END AND EVERY 25'
7) H2.5 CLIPS MISSED 10A/D-2
8) NO LADDER ACCESS TO ROOF
9) NEXT FAILURE WILL BE CHARGED A RE-FEE
10) STOPPED INSPECTION
04/06/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) CLIP GABLE END TRUSSES TO TOP PLATE AT ENDS
2) MAS STRAPS NOT NAILED
3) ROOF NOT COMPLETE
4) STOPPED INSPECTION, TOO MANY ITEMS
04/05/2005 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*