Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/25/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 05/23/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) NOT COMPLETE ENOUGH TO INSPECT, NEXT FAILURE WILL BE CHARGED A RE-FEE |
|
| 05/20/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HANGERS MISSING NAILS 2) P-2 SHEARWALL NOT NAILED PER PLAN 3) P-2 SHEARWALL MISSING ANCHOR BOLTS AT 16" ON CENTER 4) PEX NOT ALLOWED WITHIN 12" OF CAN LIGHT ENTRY 5) TOP STAIR RUN TO SHORT 6) N.E. BEDROOM SHEARWALL BOTTOM PLATE NOT BEARING ON FLOOR 7) DWV PLUMBING VENT TERMINATION MUST BE 10 FEET FROM AIR INTAKES 8) FIRESTOPS REQUIRE TWO LAYERS OF 1/2" OSB |
|
| 05/16/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) ITEMS FROM 5/11/05 NOT REPAIRED 2) STOPPED INSPECTION |
|
| 05/11/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) HANGERS MISSING NAILS 2) P-2 SHEARWALL NOT NAILED PER PLAN 3) BLOCKING PANELS NOT NAILED PER 6/SD-2 4) LVL MISSING HANGER 5) PLAN CALLS FOR LVL NOT O.S.B. AT GARAGE 6) NAIL PROTECT A/C COPPER 7) F3 TRUSS NOT BEARING AT MID POINT 8) P-2 SHEARWALL MISSING ANCHOR BOLTS UNDER STAIRS 9) PEX NOT ALLOWED WITHIN 12" OF CAN LIGHT 10) STOPPED INSPECTION, TO MANY ITEMS |
|
| 05/10/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) NOT READY PER SUPERINTENDENT |