Permit: T05CM00315

Parcel: 13216599B


Addresses:

720 E AJO WY


Inspection Status: Approved

Inspection History: SITE - SEWER

Permit Number - T05CM00315

Inspection Description - SITE - SEWER

Inspection Status - Approved

Date Description Inspector Results Comments
04/18/2006 SITE - SEWER Approved IVRS - Inspection :*
04/04/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
SEWER TO HCS TAP - OK TO COVER.
PROVIDE CONTINUOUS TRACER WIRE FROM PROPERTY LINE C/O TO HCS AND BACK TO CLEANOUT. PROVIDE LETTER CONFIRMING CONTINUITY TEST AFTER BACKFILL.
PROVIDE IRON BODY CLEANOUT AND METALLIC TAPE VISIBLE IN PROPERTY LINE CLEAN OUT.
03/31/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
SEWER LINE 80' FROM LAST C/O TO 30' NORTH OF BUILDING OK TO COVER.
03/29/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
SITE SEWER, 4" SDR TO 60' NORTH OF 4X2 JUNCTION OK.
PROVIDE SPEC FOR USE OF SDR 35.
CONTINUE RUNNING TRACER WIRE FOR ALL NON METALLIC PIPING.
03/28/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
- PROVIDE REVISED PLANS FOR SEWER.
- PROVIDE CLEANOUTS TO GRADE.
- OK TO COVER TO COMBO AT 4X2 INTERSECTION
- PROVIDE DETAIL FOR P-16 CONNECTION TO DRAIN.