Permit: T05CM00315

Parcel: 13216599B


Addresses:

720 E AJO WY


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESS TEST FNL

Permit Number - T05CM00315

Inspection Description - PLUMBING - GAS PRESS TEST FNL

Inspection Status - Approved

Date Description Inspector Results Comments
02/09/2006 PLUMBING - GAS PRESS TEST FNL Approved IVRS - Inspection :*
02/07/2006 PLUMBING - GAS PRESS TEST FNL Partial Approval IVRS - Inspection :*
PRESSURE TEST OK 9.8 PSI
CORRECTION ON VENT NOT YET MADE
SEAL WALL PENETRATION AT GAS METER
02/02/2006 PLUMBING - GAS PRESS TEST FNL Denied IVRS - Inspection :
See detailed listing on site.| 999*
IN ORDER TO DETECT A SLIGHT PRESSURE DRIP A 10 PSI TEST REQUIRES A 1/10 PSI INCREMENTATION GAUGE
TYPE B VENT REQUIRES 1" CLEARANCE FROM COMBUSTIBLE