Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/18/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/31/2006 | PLUMBING - INTERMEDIATE | Partial Approval | BACKFLOW PROTECTION FOR HOSE REELS REQUIRES AN RPA YOU HAVE A DCUA INSTALLED. |
|
| 01/18/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 12/14/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 09/26/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* WATER TEST 3" VENT AND 2" BUILDING SEWER INCLUDING SAMPLE BOX 4" DRAIN TO 5' PAST SAMPLE BOX AT ?? OR SEPARATOR. OK. | |
| 07/20/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) HOT AND COLD WATER DISTRIBUTION IN WALLS ONLY IS OK 2) AIR PRESSURE TEST 50 POUNDS ON WATER DISTRIBUTION IS OK 3) DWV SYSTEM IN PLUMBING WALLS ONLY IS OK 4) OK TO DRYWALL UPON BLDG INSPECTORS APPROVAL 5) THIS INSPECTION IS FOR THE EXISTING BLDG ONLY |