Permit: T05CM00315

Parcel: 13216599B


Addresses:

720 E AJO WY


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T05CM00315

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
03/28/2006 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
12/14/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
OVERHEAD VENT FOR GANS LAV -- OK
P-9 WASTE, VENT AND WATER PIPING TO HAND SINK - PVC SCA 40 - WATER TEST OK
RECEIVED APPROVAL OF PVC WATER LINE TO PIT FROM ARCHITECT
11/21/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*1" WATER LINE FROM SE CORNER OF BUILDING TO LOCATION OF DRAFTING PIT. PRESSURE TEST OK
TYPE L COPPER ABOVE GROUND. SHC 40 PVC BELOW GROUND
PROVIDE MATERIAL SPECS ALLOWING PVC PRESSURE PIPING
09/26/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
09/13/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) CONNECTION TO INTERCEPTOR ON INLSET SIDE OK
2) H20 AND VENT IN BLOCK AT 130, 131, 140 TO 8' AFF OK
3) 1 1/4" H20 TO P-1A AT NORTH LOCATION NEW BLDG UNDERGROUND OK
08/29/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) 3" DRAINAGE FOR (14) P-13'S + (1) P-6 STUBBED OUT OF BLDG 5' WATER TEST OK (CORRECTION MADE)
2) 2" DRAINAGE FOR P-18, P-8, P-12, P-11 WATER TEST TO 2' OUTSIDE BLDG OK
08/25/2005 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) NEW BLDG TRENCH DRAINS: REMOVE ALL CALICHI AND ROCK FROM TRENCH AND SHADE WITH CLEANFILL
2) DBL COMBO MAY NOT BE USED IN HORIZONTAL POSITION
3) ALL PIPING TO BE INSTALLED AT 2 PERCENT UNO
4) BLDG NOT PERMITTED-TO BE ON FIRM BED
08/04/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1. IN EXISTING BLDG. OVERHEAD PIPING OK
CONTRACTOR TO ADD HANGERS AND SUPPORT AS REQ'D.
2. ALL TRENCH DRAINS CONNECTED TO INTERCEPTOR DO NOT REQUIRE P-TRAPS (YOU DO NOT WANT SOLIDS CONNECTING TO THE P-TRAP)
06/17/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*P-APPROVED - 1. SOIL WATER TEST IS OK
2. BUILDING DRAIN IS STUBBED INTO 5' OF NEW BUILDING ONLY.
3. NOTE: THIS INSPECTION IS FOR ALL UNDERGROUND ROUGH SOIL IN EXISTING BUILDING ONLY.
4. OK TO BACKFILL TRENCH.