Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T05CM00315
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/28/2006 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
12/14/2005 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* OVERHEAD VENT FOR GANS LAV -- OK P-9 WASTE, VENT AND WATER PIPING TO HAND SINK - PVC SCA 40 - WATER TEST OK RECEIVED APPROVAL OF PVC WATER LINE TO PIT FROM ARCHITECT |
|
11/21/2005 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :*1" WATER LINE FROM SE CORNER OF BUILDING TO LOCATION OF DRAFTING PIT. PRESSURE TEST OK TYPE L COPPER ABOVE GROUND. SHC 40 PVC BELOW GROUND PROVIDE MATERIAL SPECS ALLOWING PVC PRESSURE PIPING |
|
09/26/2005 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* | |
09/13/2005 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1) CONNECTION TO INTERCEPTOR ON INLSET SIDE OK 2) H20 AND VENT IN BLOCK AT 130, 131, 140 TO 8' AFF OK 3) 1 1/4" H20 TO P-1A AT NORTH LOCATION NEW BLDG UNDERGROUND OK |
|
08/29/2005 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1) 3" DRAINAGE FOR (14) P-13'S + (1) P-6 STUBBED OUT OF BLDG 5' WATER TEST OK (CORRECTION MADE) 2) 2" DRAINAGE FOR P-18, P-8, P-12, P-11 WATER TEST TO 2' OUTSIDE BLDG OK |
|
08/25/2005 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1) NEW BLDG TRENCH DRAINS: REMOVE ALL CALICHI AND ROCK FROM TRENCH AND SHADE WITH CLEANFILL 2) DBL COMBO MAY NOT BE USED IN HORIZONTAL POSITION 3) ALL PIPING TO BE INSTALLED AT 2 PERCENT UNO 4) BLDG NOT PERMITTED-TO BE ON FIRM BED |
|
08/04/2005 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1. IN EXISTING BLDG. OVERHEAD PIPING OK CONTRACTOR TO ADD HANGERS AND SUPPORT AS REQ'D. 2. ALL TRENCH DRAINS CONNECTED TO INTERCEPTOR DO NOT REQUIRE P-TRAPS (YOU DO NOT WANT SOLIDS CONNECTING TO THE P-TRAP) |
|
06/17/2005 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :*P-APPROVED - 1. SOIL WATER TEST IS OK 2. BUILDING DRAIN IS STUBBED INTO 5' OF NEW BUILDING ONLY. 3. NOTE: THIS INSPECTION IS FOR ALL UNDERGROUND ROUGH SOIL IN EXISTING BUILDING ONLY. 4. OK TO BACKFILL TRENCH. |