Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T05CM00315
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/07/2006 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* 1. MISSING LB COVER OUTSIDE BY COMPRESSOR. 2. MISSING COVER PLATES FOR J-BOXES, WIREMOLD, SOUTH BAYS AREAS. 3. OPEN J-BOX, PANEL DOOR LOCKED AT MEZZ, ALSO COVER MISSING IN BAY AREA. 4. 1 LAMP NOT WORKING ON EM. LT. IN OFFICE AREA NORTH. 5. MODULAR FURNITURE NOT CONNECTED. 6. RECEPT BY H20 HTR. NOT SUPPORTED. 7. EM LTS OUTSIDE SOUTH OFFICE AREA NOT WORKING. ALSO INSIDE OFFICE AREA - LAMP OUT. 8. SUPPORT MC CABLES & CONDUITS ABOVE SOUTH OFFICE AREA AT CEILING PER CODES. 9. UNLOCK ALL POWER COVERS. 10. CLOSE UP ALL ABANDONED EQUIP. AT EXISTING SERVICE. |
|
12/06/2005 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :*OK SECONDARYS FROM SES TO TO X FORMER | |
11/09/2005 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK U.G. EAST SIDE OF BLDG, PARTIAL SOUTHWEST CHARGING CONDUIT U.G. |
|
09/26/2005 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK FEEDERS UNDER SLAB NORTH TO SOUTH AT WEST END OF NEW BLD. | |
08/11/2005 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK U.G. AT SES AREA |
|
08/04/2005 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK UNDERSLAB CONDUITS AT RAMP & STAIRS AT NEW BLD. |