Permit: T05CM00315

Parcel: 13216599B


Addresses:

720 E AJO WY


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T05CM00315

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/16/2006 BUILDING - FINAL Approved IVRS - Inspection :*
05/04/2006 BUILDING - FINAL Partial Approval IVRS - Inspection :*
OK TCO
1. ACCESSIBLE PARKING MAY NOT SLOPE MORE THAN 2%
04/25/2006 BUILDING - FINAL Partial Approval IVRS - Inspection :*
1. PROVIDE PLUMBING FINAL
2. RESOLVE ACCESSIBLE PARKING ISSUE (RELOCATE SPACES)
3. FINISH INSTALLING TRUNCATED DOMES
NOTE: TCO FOR GETTING STATION READY ONLY. STATION WILL NOT BE MANNED UNTIL PARKING & PLUMBING RESOLVED
04/19/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. TRUNCATED DOMES REQUIRED AT PARKING LOT TO SIDEWALK AND RAMP TRANSITIONS.
2. ACCESSIBLE PARKING MAY NOT SLOPE MORE THAN 2% IN ANY DIRECTION. (CURRENTLY 4.5% TO 6.5%)
3. WHEEL STOP REQUIRED AT ACCESSIBLE RAMP GUARDS.
4. RPG BACKFLOW DEVICE MUST DISCHARGE TO AN APPROVED DRAIN OR OUTSIDE OF BUILDING.