Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T05CM00311
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/12/2005 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 04/26/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* NOTE: VERIFY THRU MANUFACTURER. THAT 2X4 GRID FIX OK TO INSTALL ON COMBUSTIBLE CEILING DECK | |
| 04/25/2005 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* SEE NOTES LAST INSPECTION |
|
| 04/20/2005 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* NOTES: 1) SUPPORT J-BOXES, COMPLETE MAKE UP IN J-BOXES, SUPPORT FIXTURES TO GRID,SEE NOTES LAST INSPECTION. PROVIDE ACCESS TO ABOVE CEILING AREA,OPEN OR REMOVE CEILING TILE IN AREAS WHERE NEW CONDUIT / CIRCUITING PERFORMED |
|
| 04/18/2005 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : There is no access to the site.| 920* WHEN YOU CALL FOR INSPECTION PLEASE BE PREPARED TO RECEIVE THE INSPECTOR ON THE DAY OF INSPECTION. |
|
| 03/21/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK REST ROOM HARD LIDS ONLY. NEW OR RELOCATED GRID FIXTURES WILL REQUIRE SEISMIC WIRES & 2 SCREWS THRU GRID, 1 EACH END. | |
| 03/17/2005 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* NOT READY | |
| 03/16/2005 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |