Permit: T05CM00305

Parcel: 126071330


Addresses:

4020 E ELMWOOD ST

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
12/06/2005 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
11/22/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FRONT FAMILY ROOM NORTH EAST CORNER BRACED WALL PANEL NOT PER PLAN 20" PANEL
2) FRONT FAMILY BRACED PANEL NORTH WEST CORNER MUST BE 11'-0" PANEL
3) ALL NAILS PERTRUDE TO FAR IN BRACED PANELS
4) ALL BRACED WALL PANELS MUST BE 4'-0" PANELS
5) LOOSE BRACED WALL PANEL AT MAIN SERVICE
6) MASTER BEDROOM SOUTH EAST CORNER BRACED PANELS NOT PER PLAN
7) PROVIDE RETROFIT HOLDOWNS OR BUILD PER PLAN
11/08/2005 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) LEDGER A35'S ONLY EXCEPT STORAGE
2) MISSING A35 CLIPS STORAGE ROOM 2 X 6 AND 2 X 4 WALLS PER DETAIL 6/5 AND 1/5
11/05/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REVISED DETAIL SHOWS A35 EVERY STUD AT LEDGERS
2) A35'S MISSING MASTER BEDROOM EAST WALL DBL STUD AND HALLWAY OFF MASTER BEDROOM EAST WALL
11/01/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SHEATHING AND HOLDOWNS INCOMPLETE
2) PLAN CALLS FOR 4-16D NAILS LEDGER INTO EACH STUD
3) H2.5 NOT NAILED CORRECTLY INTO TOP OF LEDGER
4) STOPPED INSPECTION
10/25/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) H2.5 EVERY STUD PER DETAIL (1) A.35