Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/13/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 05/12/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PER ICBO REPORT ER 3878 ITEM 2.2.4.2 LATH MUST BE FURRED. SEE REFERENCE UBC TABLE 25.B NOTE 2 OR PROVIDE CITY OF TUCSON APPROVAL THAT NO FURR OUT IS REQUIRED 2) 1/2" CLEARANCE REQUIRED BETWEEN SCISSOR TRUSS AND NON BEARING WALLS 3) NO DWV WATER TEST 4) DBL SHEARWALL 2 AT M/BR NORTH SECTION, SOUTH HOLDOWN IN WRONG LOCATION 5) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACE 6) 5/DT1 NOT NAILED AT 8" ON CENTER PER PLAN |
|
| 05/06/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) LATH NOT COMPLETE 2) NAIL PROTECT CONDENSATE LINE AT TOP PLATE 3) SHEAR WALL 6 O.S.B. HAS UNSUPPORTED EDGES 4) HOLDOWN NUTS LOOSE 5) RED HEAD ANCHOR BOLTS LOOSE 6) 1/2" CLEARANCE REQUIRED BETWEEN SCISSOR TRUSS AND NON BEARING WALLS 7) NO D.W.V. WATER TEST ON PLUMBING 8) NO POTABLE WATER TEST ON PLUMBING 9) DBL SHEARWALL 2 AT MASTER BEDROOM NORTH WALL SECTION SOUTH HOLDOWN IN WRONG LOCATION 10) 5/DT1 NOT COMPLIED WITH 11) NAIL PROTECT WIRES WITHIN 1 1/4" 12) M/B EXHASUT FAN NOT IN 13) KITCHEN DRAIN DAMAGED BY STAPLES AND NAILS 14) STOPPED INSPECTION, TO MANY ITEMS |