Permit: T05CM00285

Parcel: 140383860

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
05/13/2005 FRAMING Approved IVRS - Inspection :*
05/12/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PER ICBO REPORT ER 3878 ITEM 2.2.4.2 LATH MUST BE FURRED. SEE REFERENCE UBC TABLE 25.B NOTE 2 OR PROVIDE CITY OF TUCSON APPROVAL THAT NO FURR OUT IS REQUIRED
2) 1/2" CLEARANCE REQUIRED BETWEEN SCISSOR TRUSS AND NON BEARING WALLS
3) NO DWV WATER TEST
4) DBL SHEARWALL 2 AT M/BR NORTH SECTION, SOUTH HOLDOWN IN WRONG LOCATION
5) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACE
6) 5/DT1 NOT NAILED AT 8" ON CENTER PER PLAN
05/06/2005 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) LATH NOT COMPLETE
2) NAIL PROTECT CONDENSATE LINE AT TOP PLATE
3) SHEAR WALL 6 O.S.B. HAS UNSUPPORTED EDGES
4) HOLDOWN NUTS LOOSE
5) RED HEAD ANCHOR BOLTS LOOSE
6) 1/2" CLEARANCE REQUIRED BETWEEN SCISSOR TRUSS AND NON BEARING WALLS
7) NO D.W.V. WATER TEST ON PLUMBING
8) NO POTABLE WATER TEST ON PLUMBING
9) DBL SHEARWALL 2 AT MASTER BEDROOM NORTH WALL SECTION SOUTH HOLDOWN IN WRONG LOCATION
10) 5/DT1 NOT COMPLIED WITH
11) NAIL PROTECT WIRES WITHIN 1 1/4"
12) M/B EXHASUT FAN NOT IN
13) KITCHEN DRAIN DAMAGED BY STAPLES AND NAILS
14) STOPPED INSPECTION, TO MANY ITEMS