Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/07/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* ALL CORRECTIONS HAVE BEEN MADE | |
| 06/09/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DO NOT REDUCE CONDENSATE DRAIN LINE WITH A RUBBER HOSE. TERMINATE INTO THE DRAIN WITH A 1" AIR GAP 2) PLANS CALL FOR SANYO EQUIPMENT. MCGRAY EQUIPMENT WAS INSTALLED. PROVIDE A LETTER FROM ENGINEER TO OK CHANGING EQUIPMENT 3) PROVIDE A TRAP IN THE CONDENSATE DRAIN LINE AS PER PLANS 4) PLANS SHOW REMOTE 03 SENSOR TO BE 12" AFF IN GENERATING ROOM |