Permit: T05CM00282

Parcel: 11014015A


Addresses:

2900 N CRAYCROFT RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/28/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/08/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/24/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PLANS CALL FOR ? TO BE IMC AND PER ARTICLE 500 CLASS 1 DIV 2-PLEASE PROVIDE A LETTER FOR CHANGE
2) MAINTAIN WORKING CLEARANCES PER 110.26
3) BOND PUMP MOTORS PER 680.6
4) OK ? SUBJECT TO LETTER