Permit: T05CM00279

Parcel: 10816008B


Addresses:

4980 N 1ST AV

Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Date Description Inspector Results Comments
02/21/2007 PLUMBING - SEWER HCS CONNECT Approved IVRS - Inspection :*
02/20/2007 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection :*
PROVIDE CORRECT TRANSITION GLUE FOR SDR 35 TO THIN WALL S&D BUSHING '

03040 - 1 1/4 T/K INSTALLED FROM METER LOCATION TO BUILDING. TRACER WIRE SHALL BE EXTENDED TO METER BOX WITH BACKFLOW INSTALL.
02/14/2007 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection :*
1. PIPE COVERED WITHOUT INSPECTION
NOTE: #1 FROM 1/26/07 NOT INSTALLED PER PLAN
WILL REQUIRE REVIEW OF INSTALLATION
INSTALLATION IS COVERED
2. 4" SDR 35 SITE SEWER -- REQUIRE AT LEAST 1% FILL AT CROSSING NOT APPROVED.
01/26/2007 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection :*
1. NOT INSTALLED PER PLAN
WILL REQUIRE REVIEW OF INSTALLATION
2. NO RIGHT OF WAY PERMIT ON SITE
NO PLUMBING PERMIT ON SITE