Permit: T05CM00279

Parcel: 10816008B


Addresses:

4980 N 1ST AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/18/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
NOTE: CONTRACTOR WAITING FOR 25 AMP BREAKER AND IS TO BE INSTALLED ON INSTA-HOT WHEN IT ARRIVES
ALSO, REMOVE TEMP SERVICE
04/13/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CHECK ALL PANEL DIRECTORYS MAKE SURE CORRECTLY IDENTIFIED -- NEC 408.4
2. CHECK EMERGENCY LIGHTING & OCCUPANCY SENSORS
3. CONDENSATE PUMPS TO BE ENERGIZED VIA A RECEPTACLE
NOT CUT CORD END -- NEC 400.7B
4. PROVIDE PROPER CLEARANCE FOR DISCONNECTS
NEC 110.26
5. NEED ACCESS TO PANEL "D"