Permit: T05CM00259

Parcel: 129131150


Addresses:

814 E 31ST ST #01

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
09/16/2005 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
PIPE WRAPS OK
09/14/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) WATER TEST WASTE AND VENT UNDERGROUND (ONLY) TO 2' PAST NORTH EAST CORNER OF BLDG
2) WILL NEED TO VIEW PIPE WRAPS PRIOR TO CONCRETE POUR
3) WILL NEED TO VIEW CONTINUATION OF BLDG SEWER WITH TEST AND HCS CONNECTION
09/09/2005 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLEASE PROVIDE RED LINE DRAWING OF YOUR INSTALLATION
2) PROVIDE LONG RADIUS 90 DEGREE AT VERTICAL TO HORIZONTAL DRAINAGE AT NORTH WASHING MACHINE LOCATION
3) PROVIDE CLEAN SHADING MATERIAL FOR YOUR PIPING
4) PROVIDE FULL SIZE UPPER TERMINAL CLEANOUT ON 3" FOR SOUTH UNIT
5) COMPLETE 3" SEWER BETWEEN UNITS
6) SANTEE TO P-TRAP REQUIRES 2 TIMES PIPE DIAMETER FROM VENT TO WEIR OF P-TRAP TO PREVENT S-TRAP CONDITION