Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/21/2005 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 03/09/2005 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* DO NOT CONTINUE TO TILE. 1) MEET JASON FROM ?? AND SHOWED AND EXPLAINED CODE FOR VDV CABLEING | |
| 03/04/2005 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio 1) ITEMS #1 & 4 OF PREVIOUS INSPECTIONS ARE STILL NOT DONE. A REFEE HAS BEEN ACCESSED PER ADMINISTRATIVE CODES FOR NO WORK PROGRESS. THIS IS THE 3RD INSPECTION |
|
| 02/22/2005 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOT CORRECTED AS PER 2-17-05 INSPECTION |
|
| 02/17/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SUPPORT OR REMOVE VDV CABLEING AS PER 725.2, 725, 6, 800.2, 800.6. 2) SUPPORT FLEX CONDUITS UPOFF OF GRID ROOM # 15 BREAKROOM. 3) FINISH EXIT LIGHTS. 4) WALL HAVE BEEN COVERED WITHOUT INSPECTION PLEASE VERIFY #1 OF PREVIOUS INSPECTION. |